CHILLER / HEAT PUMP Controller MACON_HPR/ HPB

  • Control device CHILLER / heat pump for 1 or 2 circuits with 2 or 4 compressors, with analog outputs 0-10 Volt in compressors and fans
  • Model MACON_HP (panel), MACON_HPR (rail) (1st circuit)
  • Μodel MACON_HPB (rail), (2nd circuit)
  • Frost monitoring where the device is OFF while the pump is ON
  • 5 PTC temperature sensors range -50 ÷ 99.9ºC, where the 3 sensors are for the first circuit, input / output water and de-Frost control and the 2 for the second circuit, water output and deFrost control
  • Decimal temperature display / Accuracy 0.5ºC
  • 9 digital inputs, 6 for the first circuit and 3 for the second
  • 7 relay outputs 250VAC 5A/3A Resistive Load in MACON_HP
  • 5 relay outputs 250VAC 5A Resistive Load in MACON_HPΒ
  • 4 analog output 0-10 Volt, 2 in each circuit for compressors (C1/C2) and fans (FAN1/FAN2) respectively
  • Cooling – heating function / Defrost function
  • ON/OFF device button
  • Alarm high – low pressure in refrigeration circuits
  • Maximum consumption for each device 10Watt
  • MACON_HP is mounted on a panel / Dimensions 28x70x75mm
  • MACON_HPΒ is mounted on a Ω rail / Dimensions 70x90x65mm
  • Connection with terminal blocks 28-16 AWG 1.5mm2
  • Power supply 24VAC/DC ± 10% 50/60Hz 5W
  • Storage temperature -20 ÷ +80ºC

TECHNICAL DATASHEET MACON_HPR